Currently, lightning protection for power lines primarily relies on the installation of zinc oxide surge arresters; however, their application presents several issues:
(1) When a zinc oxide surge arrester suffers dielectric breakdown or damage due to a lightning strike, the resulting damage point is often small and difficult to detect during routine inspections.
(2) Zinc oxide surge arresters require testing every 3 to 5 years, entailing a heavy testing workload.
(3) Zinc oxide surge arresters require grounding connections, resulting in high installation and maintenance costs.
(4) Their cost is high compared to insulators, making large-scale deployment less favorable.
To address these issues, a lightning protection device for insulators was developed. Analysis indicated that an air-gap design-characterized by structural simplicity and low cost-is well-suited for protecting line insulators. This type of air gap exploits the tendency of power-frequency arcs to rise due to their own electromagnetic forces and thermal air currents; as the arc elongates, it is eventually extinguished.
Consequently, a lightning protection device for insulators was designed, comprising an arc-initiating clamp, a positive electrode rod, and a negative electrode plate. A modular, replaceable design was adopted, separating the arc-initiating clamp from the positive electrode rod and securing them together with bolts.