1. Lifting operations: Use specialized lifting gear attached to the designated lifting points on the metal fittings; direct attachment to the porcelain body or sheds is strictly prohibited. Maintain stability during lifting and avoid collisions with hard objects.
2. Alignment and verticality control: The axial deviation for a single insulator string must not exceed 2 mm, and the overall verticality deviation must be ≤ 1‰. For parallel installations involving multiple strings, the length difference between strings must not exceed 5 mm to prevent uneven load distribution.
3. Fastening operations: Apply tightening torque strictly in accordance with fastener specifications (e.g., 80–100 N·m for M16 galvanized bolts). Avoid overtightening, which can cause the porcelain to crack, or undertightening, which can lead to loosening or detachment.